Borri Ingenio ECS

Borri

Borri Ingenio ECS (Emergency Central System) is a central power system (CPS) that has been designed in compliance with the international EN 50171 regulation. The CPS features online double conversion and a slimline design thanks to the transformer free technology.

Overview

Suitable for: Emergency lighting applications and fire and life safety systems.

Technical Specification

WARRANTY 3 Year Parts
RATING KVA 60 / 80 / 100 / 125 / 160
MAX EM LIGHTING LOAD 50 / 66 / 83 / 104 / 133
DIMENSIONS (WxDxH) 560W x 940D x 1800H
WEIGHT 250 / 300 / 320 / 360 / 380
INPUT PHASE Three Phase + Neutral
INPUT VOLTAGE 400VAC
INPUT VOLTAGE TOLERANCE RANGE -20% / +15%
INPUT FREQUENCY 50/60Hz
INPUT FREQUENCY TOLERANCE RANGE 45-65Hz
OUTPUT OUTPUT PHASE Three Phase + Neutral
OUTPUT POWER FACTOR 1
OUTPUT WAVEFORM Sinewave
OUTPUT VOLTAGE 380/400/415VAC
OUTPUT FREQUENCY 50-60Hz (Sync with mains ±2Hz)
OUTPUT EFFICIENCY ≥95% (AC-AC) / >98% (Eco mode / changeover mode) / 97% (DC-AC)
BATTERY RUNTIME Dependent on battery capacity
BATTERY DC VOLTAGE 720VDC or 744VDC
BATTERY CHARGE CAPACITY TBC (Borri yet to complete tech. specification)
MECHANICAL AC OUTLETS Hardwired
OPERATING TEMPERATURE TOLERANCE 0-40°C
STORAGE TEMPERATURE TOLERANCE -10 - +70°C
RELATIVE HUMIDITY <95% (non-condensing)
OPERATING ALTITUDE TOLERANCE <1000m
COMMUNICATION USB, RS232 and Modbus
OPTIONAL COMMS SNMP / VFC
PARALLEL Up to 6 (others on request)
FUNCTIONS EPO, Expandable Battery, Mimic LCD and keyboard, Temperature compensated charging

Resources

INGENIO ECS 30-40kVA Technical Data

INGENIO ECS 60-80-100-125-160kVA Technical Data

INGENIO ECS 60-80kVA Technical Data

Related products

Legrand Trimond MCS

3kVA - 80kVA

Modular - CPSS

Designed in accordance with EN 50171 standards, ideal for emergency and life safety systems

The Legrand Trimod MCS series is a modular centralised power system (CPS) designed in accordance with EN 50171 regulation making them the ideal solution for backing up buildings subject to fire safety standards and to power emergency lighting systems.

Borri E8031/E8033

10kVA - 50kVA

Monolithic - CPSS

Designed in compliance with EN 50171 standards, ideal for emergency and life safety systems

The Borri E8031/E8033 Emergency Central System (ECS) UPS has been designed in accordance with EN 50171 standards making them an ideal system for emergency lighting, fire and life safety applications.

CertaUPS C500E

10kVA - 20kVA

Standalone Tower

Online double conversion uninterruptible power supply with slectable input